All explosives manufacturing buildings shall be located one from the other and from other buildings on explosives manufacturing plants in which persons are regularly employed, and all magazines shall be located from factory buildings and buildings on explosives plants in which persons are regularly employed, in conformity with the intraexplosives plant quantity and distance table below set forth:
EXPLOSIVES Pounds
Over
Pounds
Not Over
Distance
Feet
Separate
Building or
Within
Substantial
Dividing Walls
. . . . 10 10 25 40 25 50 60 50 100 80 100 200 100 200 300 120 300 400 130 400 500 140 500 750 160 750 1,000 180 1,000 1,500 210 1,500 2,000 230 2,000 3,000 260 3,000 4,000 280 4,000 5,000 300 5,000 6,000 320 6,000 7,000 340 7,000 8,000 360 8,000 9,000 380 9,000 10,000 400 10,000 12,500 420 12,500 15,000 450 15,000 17,500 470 17,500 20,000 490 20,000 25,000 530 25,000 30,000 560 30,000 35,000 590 35,000 40,000 620 40,000 45,000 640 45,000 50,000 660 50,000 55,000 680 55,000 60,000 700 60,000 65,000 720 65,000 70,000 740 70,000 75,000 770 75,000 80,000 780 80,000 85,000 790 85,000 90,000 800 90,000 95,000 820 95,000 100,000 830 100,000 125,000 900 125,000 150,000 950 150,000 175,000 1,000 175,000 200,000 1,050 200,000 225,000 1,100 225,000 250,000 1,150
[1972 ex.s. c 88 § 8; 1931 c 111 § 5; RRS § 5440-5.]